The definition of terms
鈼?Open (Close) gate time:: minute open(close) tripping coil power as the starting time, the dynamic and static contact just minutes open(close) of the time.
鈼?With the same period: The same phase among the open (close) opening time difference between the maximum and minimum.
鈼?Interphase period: Three among the open (close) opening time difference between the maximum and minimum.
鈼?Average speed: Open (close) gate process, the moving contacts total stroke before and after each take 10%, to take the middle 80% of the moving contact sport stroke versus time.
鈼?Maximum speed: Open (close) gate process, the moving contacts begin to exercise, take the moving contact sport every 10ms as a speedometer unit until stopped moving contact sport, get the value of a number of speed units, the largest unit speed value is the open (close) brake maximum speed.